[go: up one dir, main page]

Skip to content

Communication between Network UPS Tools (NUT) and MQTT

License

Notifications You must be signed in to change notification settings

rburkholder/nut2mqtt

Folders and files

NameName
Last commit message
Last commit date

Latest commit

 

History

60 Commits
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Repository files navigation

nut2mqtt

Communication between Network UPS Tools (NUT) and MQTT

Uses Network UPS Tools (NUT) library

Features:

  • uses username/password, as created in /etc/nut/upsd.users, to login to the nut-server
  • will enumerate all UPS instances maintained by the service
  • will enumerate all available read-only variables, read-write variables, and commands for each instance
  • on startup, will transmit all read-only variables as a JSON map to the specified MQTT topic
  • on regular intervals, as specified in the nut2mqtt.cfg file, will transmit the variables designated as 'publish' as a JSON map to the specified MQTT topic
  • the variables marked as 'numeric' in the nutqmqtt.cfg file will be transmited as numeric (rather than a string)
  • on a broken connection to the MQTT server, a reconnections will be attempted (to be tested)

Packages to be installed (all platforms):

sudo apt install libnutclient-dev
sudo apt install libpaho-mqtt-dev

Packages (beaglebone) simply use the 'debian generic' section below, the other two sections are here as a reference:

# debian version 12.2 (not available yet)
sudo apt install libboost-filesystem1.81-dev
sudo apt install libboost-log1.81-dev
sudo apt install libboost-program-options1.81-dev
sudo apt install libboost-thread1.81-dev
# debian version 11.7 (as of 2023/10/08)
sudo apt install libboost-filesystem1.74-dev
sudo apt install libboost-log1.74-dev
sudo apt install libboost-program-options1.74-dev
sudo apt install libboost-thread1.74-dev
# debian generic
sudo apt install libboost-filesystem-dev
sudo apt install libboost-log-dev
sudo apt install libboost-program-options-dev
sudo apt install libboost-thread-dev

NOTE: my notes need revamping, but bottom line, you'll need to clone, build and install https://github.com/rburkholder/repertory first to obtain the MQTT interface. I factored it out as I found I use it across a number of my projects.

To Build statically linked application:

git clone https://github.com/rburkholder/nut2mqtt.git
cd nut2mqtt
mkdir build
cd build
cmake ..
make
cd ..
ln -s build/src/nut2mqtt nut2mqtt
# create & populate nut2mqtt.cfg with example
# then run:
./nut2mqtt

An example systemd control file can be found in systemd/nut2mqtt.service. Change working directory & executable to suit.

Configuration File template (change usernames, passwords, and addresses):

$ cat x64/debug/nut2mqtt.cfg
nut_enumerate = true    # emit found variables & commands on first iteration
nut_host = localhost
nut_username = admin
nut_password = password
nut_poll_interval = 15

mqtt_id = nut1
mqtt_host = 127.0.0.1
mqtt_username = admin
mqtt_password = password
mqtt_topic = nut

publish = battery.charge
publish = battery.voltage
publish = battery.runtime
publish = battery.temperature
publish = input.voltage
publish = output.current
publish = output.frequency
publish = output.voltage
publish = ups.load
publish = ups.status

numeric = battery.charge
numeric = battery.charge.low
numeric = battery.charge.warning
numeric = battery.runtime
numeric = battery.runtime.low
numeric = battery.temperature
numeric = battery.voltage
numeric = battery.voltage.nominal
numeric = input.voltage
numeric = input.transfer.high
numeric = input.transfer.low
numeric = input.voltage.nominal
numeric = output.current
numeric = output.frequency
numeric = output.voltage
numeric = output.powerfactor
numeric = output.frequency.nominal
numeric = output.voltage.nominal
numeric = ups.load
numeric = ups.delay.start
numeric = ups.delay.shutdown
numeric = ups.efficiency
numeric = ups.load.high
numeric = ups.power
numeric = ups.power.nominal
numeric = ups.realpower
numeric = ups.realpower.nominal
numeric = driver.parameter.pollfreq
numeric = driver.parameter.pollinterval

Sample Topic/Message Output:

nut/sm1500 {"battery.charge":100,"battery.runtime":3099,"battery.voltage":26.3,"ups.status":"OL"}
nut/sm1500 {"battery.charge":100,"battery.runtime":3202,"battery.voltage":26.3,"ups.status":"OB DISCHRG"}
nut/sm1500 {"battery.charge":89,"battery.runtime":2983,"battery.voltage":24.4,"ups.status":"OB DISCHRG"}
nut/sm1500 {"battery.charge":90,"battery.runtime":3077,"battery.voltage":24.5,"ups.status":"OL CHRG"}
nut/sm1500 {"battery.charge":90,"battery.runtime":3077,"battery.voltage":26.1,"ups.status":"OL CHRG"}

From some user on the internet: the poll interval in UPS.CONF controls the rate at which NUT queries the UPS, this is where I had my problem with my CyberPower units, the default value of 2 seconds caused my UPS to quit talking to NUT over the USB connection. I ended up with a value of 15 seconds and it has been solid for over a year of continuous operation. I did not try to tune it down to a smaller value, so I do not know what the minimum is for the CyberPower.

Inspiration:

About

Communication between Network UPS Tools (NUT) and MQTT

Resources

License

Stars

Watchers

Forks

Releases

No releases published

Packages